Cable sizing according to IEC
Calculator and step-by-step guide to choose the cross-section of a copper cable in mm² and the circuit breaker that protects it, using the current-carrying capacity table of the Spanish REBT (ITC-BT-19) and the rules of IEC 60364.
IEC calculator
Standards this guide follows
Current-carrying capacities. Spanish Low Voltage Regulation (REBT), ITC-BT-19, table 1: copper in air at 40 °C. Its values come from UNE 20460-5-523, the Spanish adoption of IEC 60364-5-523, and most manufacturers follow them. For other conditions, ITC-BT-19 refers to the UNE standard (today UNE-HD 60364-5-52, equivalent to IEC 60364-5-52).
Protection and voltage drop. IEC 60364-4-43: coordination between cable and protective device. IEC 60898-1 and IEC 60947-2: circuit breaker ratings. ITC-BT-19, section 2.2.2: maximum voltage drops.
Machines. The internal wiring of a machine and its control panel follows IEC 60204-1 (UNE-EN 60204-1 in Spain), which has its own table.
Values for copper conductors. National regulations may be stricter (in Spain the REBT, in Germany DIN VDE 0298-4, in Italy CEI 64-8, in the USA the local authority having jurisdiction). This guide is for preliminary sizing: always check the calculation against the standard and regulations that apply to your installation.
Installation for the USA or Canada? Use the cable sizing guide according to UL / NEC.
Step by step
The procedure has five steps. First you need the circuit's design current, Ib: for motors, the rated current on the nameplate; if you only know the power of a load, use the kW to amps calculator.
1. Choose the cable type
What matters most is the insulation, because it sets the maximum conductor temperature and therefore the current the cable can carry:
| Insulation | Maximum temperature | Examples |
|---|---|---|
| PVC | 70 °C | H07V-K (single-core), H05VV-F (sheathed flexible) |
| XLPE or EPR (cross-linked) | 90 °C | RV-K, RZ1-K halogen-free (Spanish designations) |
With the same cross-section, an XLPE cable carries more current than a PVC one. Many regulations require halogen-free cables in buildings open to the public.
2. Where it is installed: installation method
The standard groups the ways of installing a cable into reference methods. The worse the heat is dissipated, the less current the cable can carry:
| Method | Installation |
|---|---|
| A | Single-core conductors in conduit in a thermally insulating wall |
| A2 | Multicore cable in conduit in a thermally insulating wall |
| B | Single-core conductors in conduit or trunking on the wall, or in a panel wiring duct |
| B2 | Multicore cable in conduit or trunking on the wall |
| C | Cable clipped directly to the wall or ceiling, or on an unperforated tray |
| E | Multicore cable in free air: perforated tray, wire mesh tray or cable ladder |
| F | Single-core cables touching in free air or on a perforated tray (from 25 mm²) |
| G | Spaced single-core cables in free air (from 25 mm²) |
A wire mesh (basket) tray counts as a perforated tray: method E for multicore cables and F for single-core cables. Buried cables (method D) have their own table and are not covered here.
3. Correct for temperature and grouping
Table 1 of ITC-BT-19 gives the current-carrying capacity Iz0 in air at 40 °C with a single circuit. If the temperature is different or several circuits run together, multiply by two factors:
Iz = Iz0 × kT × kG
The temperature factor is kT = √((θmax − θ) / (θmax − 40)), with θmax = 70 °C for PVC and 90 °C for XLPE.
Factor kT for ambient temperature, referred to 40 °C
| Insulation | 25 °C | 30 °C | 35 °C | 40 °C | 45 °C | 50 °C |
|---|---|---|---|---|---|---|
| PVC | 1.22 | 1.15 | 1.08 | 1.00 | 0.91 | 0.82 |
| XLPE or EPR | 1.14 | 1.10 | 1.05 | 1.00 | 0.95 | 0.89 |
Factor kG for the number of grouped circuits (table B.52.17)
| Installation | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
|---|---|---|---|---|---|---|---|---|---|
| In conduit, bunched or embedded (methods A and B) | 1.00 | 0.80 | 0.70 | 0.65 | 0.60 | 0.57 | 0.54 | 0.52 | 0.50 |
| Single layer on the wall (method C) | 1.00 | 0.85 | 0.79 | 0.75 | 0.73 | 0.72 | 0.72 | 0.71 | 0.70 |
| Single layer on a perforated tray (method E) | 1.00 | 0.88 | 0.82 | 0.77 | 0.75 | 0.73 | 0.73 | 0.72 | 0.72 |
4. Choose the upstream circuit breaker
The circuit breaker protects the cable against overload. IEC 60364-4-43 requires its rating In to lie between the circuit current and what the cable can carry:
Ib ≤ In ≤ Iz
The standard's second condition, I2 ≤ 1.45 × Iz, is met automatically by circuit breakers to IEC 60898-1, because their conventional tripping current is 1.45 × In. Standard ratings: 6, 10, 13, 16, 20, 25, 32, 40, 50, 63, 80, 100 and 125 A.
| Curve | Magnetic trip | Typical use |
|---|---|---|
| B | 3 to 5 × In | Resistive loads, lighting, long lines |
| C | 5 to 10 × In | General use, small motors, power supplies |
| D | 10 to 20 × In | Very high inrush: transformers, large motors |
Single-phase circuits use a 1-pole + neutral or 2-pole breaker; three-phase circuits, a 3- or 4-pole breaker. Motors are usually protected by a motor protection switch set to the motor's rated current.
5. Check the voltage drop
If the cable is long, the voltage reaching the load can drop too much. It is calculated like this:
u = b × (ρ × L / S × cos φ + λ × L × sin φ) × Ib ΔU (%) = 100 × u / U0
b = 1 for three-phase and 2 for single-phase; ρ = 1/γ, with γ = 48 m/(Ω·mm²) for copper at 70 °C (PVC) and 44 for copper at 90 °C (XLPE); λ = 0.08 mΩ/m; L in metres; S in mm²; U0 = 230 V. ITC-BT-19 limits: 3 % for lighting and 5 % for other uses (3 % in dwellings); in industrial installations with their own transformer, 4.5 % and 6.5 %. If it is not met, increase the cross-section.
Worked example
7.5 kW motor, 400 V three-phase, Ib = 14.15 A; XLPE cable on a wire mesh tray with two other circuits (method E, 3 circuits), 35 °C ambient and 80 m long.
- Circuit breaker: the standard rating equal to or above 14.15 A is
In = 16 A. - Factors:
kT = 1.05(XLPE at 35 °C, referred to 40 °C) andkG = 0.82(3 circuits on a perforated tray). - 1.5 mm²: column 9 of the table,
Iz = 21 × 1.05 × 0.82 = 18.1 A ≥ 16 A, but the voltage drop is 6.36 %: it fails. - 2.5 mm²:
Iz = 29 × 1.05 × 0.82 = 25.0 Aand a 3.82 % drop: it passes. 2.5 mm² cable and 16 A circuit breaker.
Current-carrying capacity table (REBT)
Table 1 of ITC-BT-19, with the same columns 1 to 11 as the regulation. The first table shows which column each method uses; the second gives the current-carrying capacity Iz0. 3× = three loaded conductors (three-phase); 2× = two loaded conductors (single-phase).
Table column for each installation method
| Method | 3×PVC | 2×PVC | 3×XLPE | 2×XLPE |
|---|---|---|---|---|
| A | 2 | 3 | 5 | 6 |
| A2 | 1 | 2 | 4 | 5 |
| B | 4 | 5 | 8 | 9 |
| B2 | 3 | 4 | 6 | 8 |
| C | 5 | 6 | 8 | 9 |
| E | 6 | 8 | 9 | 10 |
| F | 7 | – | 10 | – |
| G | 9 | – | 11 | – |
Current-carrying capacity (A) per column, copper, in air at 40 °C
| Cross-section (mm²) | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.5 | 11 | 11.5 | 13 | 13.5 | 15 | 16 | – | 18 | 21 | 24 | – |
| 2.5 | 15 | 16 | 17.5 | 18.5 | 21 | 22 | – | 25 | 29 | 33 | – |
| 4 | 20 | 21 | 23 | 24 | 27 | 30 | – | 34 | 38 | 45 | – |
| 6 | 25 | 27 | 30 | 32 | 36 | 37 | – | 44 | 49 | 57 | – |
| 10 | 34 | 37 | 40 | 44 | 50 | 52 | – | 60 | 68 | 76 | – |
| 16 | 45 | 49 | 54 | 59 | 66 | 70 | – | 80 | 91 | 105 | – |
| 25 | 59 | 64 | 70 | 77 | 84 | 88 | 96 | 106 | 116 | 123 | 166 |
| 35 | – | 77 | 86 | 96 | 104 | 110 | 119 | 131 | 144 | 154 | 206 |
| 50 | – | 94 | 103 | 117 | 125 | 133 | 145 | 159 | 175 | 188 | 250 |
| 70 | – | – | – | 149 | 160 | 171 | 188 | 202 | 224 | 244 | 321 |
| 95 | – | – | – | 180 | 194 | 207 | 230 | 245 | 271 | 296 | 391 |
| 120 | – | – | – | 208 | 225 | 240 | 267 | 284 | 314 | 348 | 455 |
| 150 | – | – | – | 236 | 260 | 278 | 310 | 338 | 363 | 404 | 525 |
| 185 | – | – | – | 268 | 297 | 317 | 354 | 386 | 415 | 464 | 601 |
| 240 | – | – | – | 315 | 350 | 374 | 419 | 455 | 490 | 552 | 711 |
| 300 | – | – | – | 360 | 404 | 423 | 484 | 524 | 565 | 640 | 821 |
Common questions
Can I use a circuit breaker rated higher than the cable's current-carrying capacity?
No. The rating must be less than or equal to the cable's corrected current-carrying capacity (In ≤ Iz); otherwise the cable can overheat without the breaker tripping.
Which method applies to a cable on a wire mesh tray?
A multicore cable on a wire mesh or perforated tray falls under method E of IEC 60364-5-52. Single-core cables use method F, with its own table.
What about short-circuit protection?
The cable must also withstand the short-circuit current until the protection operates (IEC 60364-4-43), and the breaker must disconnect in time in the event of a fault (IEC 60364-4-41). Check it with your installation's data.
Links
- REBT (Royal Decree 842/2002) · Spanish Low Voltage Electrotechnical Regulation and its ITCs, consolidated text (BOE)
- IEC 60364-5-52 · Selection and erection: wiring systems (official IEC page)
- IEC 60364-4-43:2023 · Protection against overcurrent (official IEC page)
- IEC 60898-1 · Circuit breakers for household and similar installations (official IEC page)
- kW to amps calculator · FaseCAD tool
- Cable sizing according to UL / NEC · FaseCAD guide