Stop paying for reactive power
Work out in seconds the kvar of the capacitor bank you need to raise the power factor, how much the current in your lines drops and the capacitance of each capacitor.
Calculator
What you gain by compensating
- No more surcharge. Many utilities charge for reactive energy when the power factor falls below a limit, typically 0.9 to 0.95. In Spain, for supplies above 15 kW, it is billed when reactive energy exceeds 33 % of active energy, which is exactly a cos φ of 0.95.
- Less current. Less current flows for the same useful power: cables, protective devices and the transformer have more headroom and can take more load.
- Lower losses. Cable losses go with the square of the current: cutting the current by 20 % reduces them by more than 35 %.
- Lower voltage drop on long lines, especially with large motors.
Formulas
The reactive power the capacitor bank has to supply is:
Qc = P × (tan φ1 − tan φ2) = P × k
P is the active power in kW; φ1 and φ2, the angles of the current and target power factor; and tan φ = √(1 − cos² φ) / cos φ. The capacitance of each capacitor, with ω = 2π × f:
| System | Capacitance per capacitor | Bank current |
|---|---|---|
| Three-phase, three capacitors in delta | C = Qc / (3 × ω × U²) | Ic = Qc / (√3 × U) |
| Single-phase | C = Qc / (ω × U²) | Ic = Qc / U |
The line current drops in proportion to the power factors, I2 = I1 × cos φ1 / cos φ2, and cable losses with the square of that ratio.
Worked example
- Data: a workshop drawing 50 kW at 400 V three-phase with cos φ 0.75; the target is 0.95.
- Factor k:
tan φ1 = 0.882andtan φ2 = 0.329, sok = 0.553. - Bank:
Qc = 50 × 0.553 = 27.66 kvar; in practice, a standard 30 kvar bank. - Result: the current drops from 96.23 A to 75.97 A (21 % less) and cable losses by 37.7 %.
Table of k factors
Multiply the active power in kW by the factor in the table to get the kvar needed:
Factor k from the current cos φ (rows) to the target (columns)
| Current cos φ | 0.90 | 0.92 | 0.95 | 0.98 | 1.00 |
|---|---|---|---|---|---|
| 0.50 | 1.25 | 1.31 | 1.40 | 1.53 | 1.73 |
| 0.55 | 1.03 | 1.09 | 1.19 | 1.32 | 1.52 |
| 0.60 | 0.85 | 0.91 | 1.00 | 1.13 | 1.33 |
| 0.65 | 0.68 | 0.74 | 0.84 | 0.97 | 1.17 |
| 0.70 | 0.54 | 0.59 | 0.69 | 0.82 | 1.02 |
| 0.75 | 0.40 | 0.46 | 0.55 | 0.68 | 0.88 |
| 0.80 | 0.27 | 0.32 | 0.42 | 0.55 | 0.75 |
| 0.85 | 0.14 | 0.19 | 0.29 | 0.42 | 0.62 |
| 0.90 | – | 0.06 | 0.16 | 0.28 | 0.48 |
Common questions
What is reactive power?
The energy that motors, transformers and reactors need to build their magnetic field. It does no useful work, but it flows through cables and the transformer and loads them just like active power.
Up to what cos φ should I compensate?
The usual target is 0.95, the limit above which many utilities stop charging the surcharge. Going beyond 0.98 costs a lot for little gain, and reaching 1 or overcompensating can cause overvoltages at light load.
Fixed or automatic bank?
Fixed for a constant load, such as a motor that always runs or a transformer's no-load consumption. Automatic, with steps switching in and out with demand, when the load changes during the day.
What if there are harmonics?
Capacitors can resonate with harmonics from power electronics and become overloaded. In such installations detuned banks (with blocking reactors) are used: ask the manufacturer.
How do I find my current cos φ?
From the electricity bill (active and reactive energy for the period: cos φ = kWh / √(kWh² + kvarh²)), from the power analyser in the main switchboard or, for a motor, from its nameplate.
Links
- kW to amps calculator · FaseCAD tool
- Cable sizing according to IEC · FaseCAD guide