Reference designation according to IEC 81346

How to name each device in an electrical schematic so that anyone can tell, just by reading its name, what it is, which part of the installation it belongs to and where it is.

IEC 81346-1:2022 · IEC 81346-2:2019

What a reference designation is

It is the unique name that identifies each device throughout the documentation of an installation: in the schematic, on the panel label, in the bill of materials and in the terminal plan. The IEC 81346 standard (EN IEC 81346 in Europe) sets how that name is built, so that it is the same in every document and every discipline: electrical, mechanical or process.

The series has two main parts. Part 1 gives the rules for structuring the installation and writing designations. Part 2 defines the letters that indicate each device's class. IEC 81346 replaced the former IEC 61346, and its letter table replaced those of earlier standards such as IEC 60750, which is where still very common names like K1 for a contactor come from.

The three aspects: =, + and -

The same device can be seen from three points of view, which the standard calls aspects. Each one is written with its own prefix sign:

SignAspectAnswersExample
=FunctionWhat is it for? Which part of the installation does it belong to?=A1 production line 1
+LocationWhere is it physically?+CP1 panel 1
-ProductWhich device is it?-Q1 switch 1

How they combine

The aspects are written one after another. A full designation reads like this:

=A1in line 1 +CP1inside panel 1 -Q1switch Q1

Each aspect can have several levels by repeating the sign: -A1-K2 is relay K2, which is part of device A1.

You do not always need to write the full designation. In a schematic that already belongs to =A1 and +CP1, -Q1 is enough; the full designation is used in reports, labels and wiring between panels.

Class letters according to IEC 81346-2

The letter after the - sign indicates the device's class according to its inherent function, that is, what the device does by itself, regardless of what it is used for in your installation. These are the entry classes of IEC 81346-2:2019:

LetterInherent functionExamples
BPicking up information and providing a representationSensors, instrument transformers, limit switches
CStoring for subsequent retrievalCapacitors, batteries, tanks
EEmitting light, heat or other radiationLighting lamps, heaters
FProtecting against dangerous or undesirable conditionsFuses, surge protective devices
GProviding a controllable flowGenerators, pumps, fans
HTreating matterFilters, mixers
KTreating input signals and providing an appropriate outputPLCs, auxiliary relays, controllers
MProviding mechanical movement or forceMotors, cylinders, actuators
NEnclosing another object partly or fullyCovers, housings, lids
PProviding perceptible informationIndicator lights, displays, gauges, buzzers
QControlling access or flowContactors, circuit breakers, motor protection switches, valves
RRestricting or stabilisingResistors, diodes, non-return valves
SDetecting a human action and providing an appropriate responsePush buttons, selector switches, keypads
TTransformingTransformers, frequency converters, power supplies
ULocating and holding other objectsBrackets, DIN rails, fixings
WLeading from one place to anotherCables, conductors, busbars
XInterfacing objectsTerminals, terminal strips, connectors, sockets

The letters A, I and O are not used as classes, and D, J, L, V, Y and Z are reserved for the future. The standard adds two- and three-letter subclasses for more detail: for example BT for temperature sensors, BG for position detectors or CA for capacitors.

From classic notation to IEC 81346-2

Many panels are still drawn with the classic notation, and FaseCAD's example templates use it because it is the one most often found in real drawings. These are the same devices with the current letters:

DeviceClassic notationIEC 81346-2
Motor protection switchQ1-Q1
ContactorKM1-Q2
Three-phase motorM1-M1
Push buttonS1-S1
Indicator lightH1-P1
Auxiliary relayK1-K1
Inductive sensorB1-B1
Terminal stripX1-X1

The two most visible changes: contactors move from K to Q, because they control a flow of energy, and indicator lights move from H to P, because they provide information.

Designation in FaseCAD

In FaseCAD every symbol carries its designation and can be numbered automatically. The full structure by function, location and product according to IEC 81346, with navigators to find any device, terminal or cable, is planned.

Common questions

Is IEC 81346 mandatory?

In general it is not required by law, but it is the international reference for designating devices, and many customers and engineering firms require it in their specifications.

What is the difference between = and +?

The = sign says which function or part of the installation the device belongs to; the + sign says where it physically is. One panel (+CP1) can house devices from several functions (=A1, =A2).

Do I have to use the two-letter subclasses?

No. The standard lets you use just the entry-class letter or refine it with two or three letters. What matters is that the whole project follows the same rule.