Calculator

Convert kW to amps

Work out the current from the power, or the power from the current, for DC, single-phase and three-phase circuits. With the formulas, worked examples and a table of common values.

Calculator

What do you want to calculate
Result 16.98 A I = 10 × 1000 / (√3 × 400 × 0.85)

In three-phase, the voltage is the line-to-line voltage. Leave efficiency at 100 % if you know the electrical power; for a motor's rated power (mechanical, at the shaft), enter its efficiency.

Formulas

P is the power in kW, V the voltage in volts, I the current in amps, cos φ the power factor and η the efficiency.

SystemkW to ampsAmps to kW
DCI = P × 1000 / VP = V × I / 1000
Single-phaseI = P × 1000 / (V × cos φ)P = V × I × cos φ / 1000
Three-phaseI = P × 1000 / (√3 × V × cos φ)P = √3 × V × I × cos φ / 1000

If P is a motor's mechanical power, also divide by the efficiency: in three-phase, I = P × 1000 / (√3 × V × cos φ × η). √3 is approximately 1.732.

Worked examples

  1. 7.5 kW motor at 400 V three-phase, cos φ 0.85, efficiency 90 %. I = 7500 / (1.732 × 400 × 0.85 × 0.90) = 14.15 A
  2. 2 kW heater at 230 V single-phase (cos φ 1). I = 2000 / 230 = 8.70 A
  3. Power of a 32 A three-phase line at 400 V with cos φ 0.9. P = 1.732 × 400 × 32 × 0.9 / 1000 = 19.95 kW

kW to amps table

Current in amps for loads of common power ratings:

Power (kW)Single-phase 230 V
cos φ = 1
Three-phase 400 V
cos φ = 1
Three-phase 400 V
cos φ = 0.85
0.371.610.530.63
0.753.261.081.27
1.14.781.591.87
1.56.522.172.55
2.29.573.183.74
313.044.335.09
417.395.776.79
5.523.917.949.34
7.532.6110.8312.74
1147.8315.8818.68
1565.2221.6525.47
18.580.4326.7031.41
2295.6531.7537.36
30130.4343.3050.94
37160.8753.4062.83
45195.6564.9576.41
55239.1379.3993.39
75326.09108.25127.36
90391.30129.90152.83
110478.26158.77186.79

The values are the current of a load with that electrical power. A motor's rated current is somewhat higher, because its stated power is the mechanical output: always check its rating plate.

Common questions

How many amps is 1 kW?

It depends on the voltage and the system: at 230 V single-phase with cos φ 1 it is 4.35 A; at 400 V three-phase with cos φ 1 it is 1.44 A.

What is the power factor for?

In AC circuits, motors and coils also draw reactive power, so the current is higher than the active power alone suggests. The cos φ accounts for that difference; for purely resistive loads it is 1.

Which voltage do I use for three-phase?

The line-to-line voltage (for example 400 V in Europe), not the line-to-neutral voltage (230 V).

How do I convert kVA to amps?

With the same formula and cos φ = 1: kVA is apparent power and already includes the power factor.

Can I use it to choose the cable or the protection?

It gives the operating current, which is the starting point. Cable cross-section and protection also depend on the installation method, temperature, length and local regulations.